NXMK Handheld analog circuit breaker
1、Device Overview
The NXMK handheld simulated circuit breaker is primarily used for full-system testing of relay protection devices, as well as for replacing actual circuit breakers in other test applications; it serves as a substitute for the actual circuit breaker when conducting full-system switching system transmission tests for relay protection and automatic protection devices. It offers accurate and reliable operation with no limit on the number of operations, thereby significantly improving test accuracy and completeness, minimizing the number of operations required of the actual circuit breaker, and extending its service life. This simulation device can be used in conjunction with a relay protection verification device or independently. The equipment is powered by a lithium battery and can operate in dual-unit parallel configuration.
2、Main features
1)Powered by a lithium battery, making it convenient to carry and use on-site.
2)Provide one set of opening coils and one set of closing coils.
3)Built-in manual opening/closing function
4)The opening and closing times can be set, as can the energy storage duration.
5)Equipped with one set of closing contacts, one set of opening contact outputs, and one set of non-energy-storage operation contacts.
6)Features one permanent-magnet input terminal
7)Microcontroller-based microcomputer control systems can undergo intelligent upgrades and meet a wide range of requirements.
8)The high-performance hardware platform utilizes industrial-grade standard components for its primary parts and military-grade components for its core elements, ensuring the high quality of the system.
3、Key Technical Parameters1)Operating power supply voltage: Powered by a lithium battery; charging voltage: 12 V.
2)Output quantity nodes: the circuit breaker position output provides one pair of closing positions, one pair of opening positions, and one pair of non-energy-storage positions, all of which are mutually independent.
3)Breaker and closing input voltage: DC 48–250 V, AC 20–220 V.
4)Opening and closing time: 5 ms–1000 ms, settable as desired; tolerance shall not exceed ±2 ms.
5)Manual opening and closing switch.
6)Output node: contact capacity: DC 220 V/1 A, AC 220 V/5 A.